Digital Flow Switch
Features of Digital Differential Pressure Type Split-display Flow Meter:
- 1.Horizontal display function. 2.Split display, optimized visibility.
- Detail
- Code of order
| Item/Model | FPMD | |||
|---|---|---|---|---|
| Flow rate | L/min | 50 | 100 | 200 |
| Port size | Ø6, Ø8 | Ø8 | ||
| Measure fluid | Air, Nitrogen | |||
| Flow unit | Display | 2 color LCD | ||
| Displayable range | 0~50 | 0~100 | 0~200 | |
| Min. display unit | 0.1 | 1 | ||
| Accumulated pulse f low function | Displayable range | 999999.9 | 9999999 | |
| Min. display unit | 0.1 | 1 | ||
| Power Type | Voltage | DC24V (±10%) | ||
| Current consumption | 50 mA or below | |||
| Response time | 50 ms or below | |||
| Environment | Min. operating pressure | 0.1 | ||
| Max. operating pressure | 0.7 | |||
| Proof pressure | 1 | |||
| Ambient of fluid temperature/humidity | 0 ~ 50 (No ice, no frost) / 90% or below | |||
| Operating temperature range | 0 ~ 50℃ | |||
| Accuracy | Operating range | 3 ~ 100%F.S. | ||
| Linearity | within ±3%(The secondary atmospheric release) | |||
| Pressure characteristics | ±2% | |||
| Temperature characteristics | within ±0.2%F.S/℃ (15~35℃ , 25℃ base) | |||
| Repeatability | within ±1% | |||
| Output type | Analog output | Voltage output: 1 ~ 5 V, Load Impedance: 50 kΩ | ||
| Wiring | Ø3.8mm, AWG26 X 5 Core | |||
| Enclosure | IP40 | |||
| Circuit protection | Reverse power connect protection | |||
| Weight | G | 56 | ||