FCD-Separable Numeric Display Flow Switch (Mass Flow Type)

Features of Separable Numeric Display Flow Switch (Mass Flow Type):

  • 1. Adopting the connection type, simple wiring.
    2.Installation is unlimited
    3. Display interface can be centrally installed and managed

FCD-Separable Numeric Display Flow Switch (Mass Flow Type)
  • Detail
  • Code of order
Setting flow range-ml 5,10,50,100,500
Setting flow range-l 1,2,4,5,10,12,20,25,32,50,100,200,500,1000,1500
Ambient of fluid temperature and humidity(°c) 0~50
Display type 4 digit + 4 digit; 2 color LCD display
Input voltage 0.5~4.5V
Output type-Analog output 0.5 ~ 4.5 V voltage output 1 point (load impedance 50k Ω above)
Output type-Switch output 2 NPN open collector output, 50mA or below, voltage dropping
Power supply voltage DC12~24V (10.8~26.4V)
Current consumption Below 40mA (when reach to DC24V, load impedance )
Wiring Ø 3.7 is AWG 26 x 5 core (connector), insulator outter dia. Ø 1.0
Function Flow display, flow display to peak holding, on-off output, analog output
Enclosure IEC standard equal to IP 40
Circuit protection Reverse power connect protection
Accessory 1 sensing connector with 1 meter cable
Weight (body only) about 16g
UnSelected
Selected
Correct model
P/N incomplete
FCD-Separable Numeric Display Flow Switch (Mass Flow Type)
- +

*Please select the required specifications in order, and the corresponding products will be generated below.

1
2
3
4
5
L O A D I N G