| Applicable Fluid | Filtered air,Non-corrosive/Non-flammable gas |
| Rated Pressure Range | -100.0 ~ 100.0kPa | 0.0 ~ -101.3 kPa | 0.000 ~ 1.000 MPa |
| Set Pressure Range | -101.0 ~ 101.0kPa | 10.0 ~ -101.3 kPa | -0.100 ~ 1.000 MPa |
| Withstand Pressure | 300 kPa | 1.5 MPa |
| Set pressure resolution | kPa | 0.1 | - |
| MPa | - | 0.001 |
| kgf/cm² | 0.001 | 0.1 |
| bar | 0.001 | 0.1 |
| psi | 0.01 | 0.1 |
| inHg | 0.1 | - |
| mmHg | 1 | - |
| Power supply voltage | 12 to 24V DC ±10%,Ripple (P-P) ≤10% or less |
| Current consumption | ≤ 40 mA(with no load) |
| Switch Output | 2NPN open collector outputs Max.Load Current : 125mA Max. Supply Voltage : 30VDC Residual Voltage : ≤1.5V | 2NPN open collector outputs Max.Load Current : 125mA Max. Supply Voltage : 24VDC Residual Voltage : ≤1.5V |
| Repeatability | ±0.2% F.S. ±1 digit or less |
| Hysteresis | OPS mode | Adjustable |
| Hysteresis mode |
| Window comparator mode |
| Response time | ≤ 2.5ms (chattering-proof function : 25ms, 100ms 500ms and 1500 ms selectable) |
| Output short circuit protection | Yes |
| Display | 3 colors display (Red,Green,Orange) ( Samping rate : 5 times/sec.) |
| Indicator accuracy | ±2% F.S. ±1 digit (ambient temperature :25 ±3°C) |
| Switch on lndicator | Orange indicator 1: OUT 1,Orange indicator 2: OUT 2 |
| Analog output (Voltage output) | Output voltage: 1 ~ 5V ±2.5% F.S.(within rated pressure range) Linearity: ±1% F.S Output impedance : approx.1kᘯ |
| Analog output (Current output) | Output current : 4~20mA ±2.5%F.S.(within rated pressure range)Linearity :±1%F.S. Max.Load Impedance : 300ᘯ at power supply of 12v /600ᘯ at power supply of 24V Min.Load Impedance : 50ᘯ |
| Environ-mental Resistance | Enclosure | IP 40 |
| Ambient temp.range | Operating : 0 ~ 50℃,Storage : - 10 ~ 60℃(No condensation or freezing) |
| Ambient humidity range | Operating & Storage : 35 ~ 85%RH (No condensation ) |
| Withstand voltage | 1000V AC in 1-min (between case and laed wire) |
| Insulation | 50MΩ (500V DC) (between case and laed wire) |
| Vibration | Total amplitude 1.5mm or 10G,10Hz ~ 55Hz ~ 10Hz scan for minute,2 hours each direction of X、Y、Z |
| Impact | 100 m/s² (10G) 3 times each in direction of X、Y、Z |
| Temperature characteristic | ±2% F.S. of detected pressure(25℃) at temp.Range of 0~50℃ |
| Connection Port | R:R1/8"(Rc1/8"),M5; NPT:1/8",10~32UNF ; G:G1/8" ;M5 |
| Lead wire | Oil -resistance cable ( 0.15 mm² ) |
| Weight(G) | Approx. 80g |